Quenchfire designs and manufactures the Halo2 high-pressure water mist system in Britain. Since 2012 we have installed more than 5,000 systems, supporting developers, fire engineers, Building Control and housing providers from concept design to long-term maintenance.
PUMP UNIT · MODEL 2.0
Fire tested by the FPA
Report 103857.001
[FURTHER ACCREDITATIONS]
Whether you are specifying, approving, commissioning or living with a system, start where the information is most relevant to you.
The standards framework for residential water mist changed in 2025. Here is a plain statement of what is current, what has been withdrawn, and how Halo2's independent fire test evidence should be read.
The former UK code of practice for residential and domestic watermist systems. BSI withdrew it in 2025 on publication of EN 14972-17. It is no longer the current standard for residential water mist.
Fixed firefighting systems – Water mist systems – Part 17: Test protocol for residential occupancies for automatic nozzle systems. Part of the EN 14972 series, alongside Part 1 for design, installation, inspection and maintenance.
EN TESTING · EARLY 2027
In September 2022 the Fire Protection Association tested Halo2 to the BS 8458:2015 Annex C room fire tests. It met the clause 6.1 recommendations in all six scenarios. That evidence remains relevant, independent technical evidence for fire engineers; it is not a claim of compliance with EN 14972-17. Our EN 14972-17 test programme is in its final design stage, with completion expected in early 2027.
“It should not be inferred simply from the withdrawal of BS 8458:2015 that products manufactured to the standard or certification schemes developed to the standard can no longer be used or recognised following the publication of EN 14972-17:2025.”
| BS 8458 Annex C scenario | Max. ceiling temp. (limit 320 °C) | Max. at 1.6 m (limit 95 °C) | Clause 6.1 |
|---|---|---|---|
| A · Corner | 125.8 °C | 55.5 °C | Met |
| B · Between two nozzles | 201.2 °C | 38.8 °C | Met |
| C · Beneath a nozzle | 50.7 °C | 47.8 °C | Met |
| D · Ventilation | 126.5 °C | 37.1 °C | Met |
| E1 · Open room 1 | 299.9 °C | 26.8 °C | Met |
| E2 · Open room 2 | 138.5 °C | 20.3 °C | Met |
Summary only. Tested in an 8 × 4 m compartment; the report places the BS 8458 application limit at rooms up to 80 m² with ceilings up to 3.5 m. The full 50-page report, including test observations and scope, is supplied in full on request.
High-pressure water mist breaks water into very fine droplets that absorb heat rapidly and displace oxygen at the fire, controlling it with far less water than a conventional sprinkler. Halo2 brings that technology to homes and residential buildings with a compact pump unit and discreet automatic nozzles.